McQuay MCK030A Manual do Utilizador Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
9
NOTES
1. At the following nominal conditions: 7/12°C inlet/outlet water temperature; 27°C db / 19°C wb inlet air temperature; high speed
2. At the following nominal conditions: 50°C inlet water temperature; 20°C inlet air temperature; same water flow as for cooling; high speed
3. At nominal air flow; high/medium/low fan speed; 1m in front of the unit; 0.8 m below the unit; (according to JIS C9612 standards)
MODEL MWM 005FW 007FW 010FW 015FW 020FW 025FW
Nominal Air Flow
(High-Medium-Low)
Total Cooling Capacity
1
Sensible Cooling Capacity
1
Heating Capacity
2
Water Flow
Water Pressure Drop -Cooling
Lp (Sound Pressure Level)
3
Power Input
Current Input
Power Supply
Water Connections Diameter
Condensate Drain Connection
Weight
m
3
/h
kW
kW
kW
l/s
kP
a
dB(A)
kW
A
V/ph/Hz
in
in
kg
340/239/238
1,4
1,2
2,2
0,059
3
37/33/28
0,023
0,10
3/4"
1/2"
10
340/289/238
2,0
1,5
2,4
0,084
6
38/34/30
0,023
0,10
3/4"
1/2"
11
460/390/320
2,8
2,1
3,5
0,121
16
38/34/30
0,025
0,1
1
3/4"
1/2"
12
220-240/1/50
510/460/390
3,5
2,5
4,0
0,154
25
38/35/31
0,025
0,1
1
3/4"
1/2"
12
820/730/630
5,0
3,7
5,7
0,233
27
45/42/39
0,053
0,23
3/4"
1/2"
15
990/820/650
6,2
4,5
7,0
0,257
18
47/44/42
0,057
0,24
3/4"
1/2"
15
Technical Data
MODELLO MWM 005FW 007FW 010FW 015FW 020FW 025FW
A
B
C
D
E
mm
mm
mm
mm
mm
815
290
181
70
50
815
290
181
70
50
815
290
181
70
50
815
290
181
70
50
1062
306
202
80
50
1062
306
202
80
50
Dimensions
A
B
C
D
E
Chilled Water Fan Coils
The MWM series delivers a high standard of air
quality characteristics in all applications. The
automatic control of the airflow direction allows
distribution into every corner of the room. The three-
stage active filtration, removes dust and particles with
diameters down to 0.01 micron.
Its ionised filter
prevents potential bacteria proliferation and
minimises unpleasant smells, maintaining a clean and
healthy environment. The use of random-pitched fan
blades makes the MWM models extremely quiet. All
key components can be accessed by simply removing
the front
cover, easily facilitating routine service tasks
such as grille and filter cleaning. Detection and
identification of any potential non-correct operation is
signalled by a blinking LED on the remote display.
MWM - Wall Mounted
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 19 20

Comentários a estes Manuais

Sem comentários