MWM-J _ (ii)Supercedes:MWM-J-2010Wall Mounted Split SystemsModels:MWM09J/JRMWM15J/JRMWM20J/JRMWM25J/JRM5WM10J/JRM5WM15J/JRM5WM20J/JRM5WM25J/JRCatalog
8MWM-J_(ii) Application InformationModel: MWM20JR - MLC20CRModel: MWM15JR - MLC15CR 70034 095236
9Application Information MWM-J_(ii)Model: M5WM20J – M5LC20CJModel: M5WM25J – M5LC25CJ
10MWM-J_(ii) Application InformationModel: MWM25JR - MLC25CRCHECK JOINTCOOLING & HEATINGCAP TUBEModel: M5WM20JR – M5LC20CRJCHECK JOINTHEATING CAP
11Application Information MWM-J_(ii)Model: M5WM25JR – M5LC25CRJ CHECK JOINTCOOLING & HEATINGCAP TUBE
12MWM-J_(ii) Application InformationInstallation GuidelineSafety Precautions WARNING CAUTION• Installation and maintenance should be performed by qu
13Application Information MWM-J_(ii)CautionBefore installing the unit, ensure that the power supply matches the power requirement of the air conditi
14MWM-J_(ii) Application InformationCooling Unit (single phase)COMPN1COMPNNLOutdoor UnitTerminal BlockIndoor UnitTerminal BlockThere must be a double
15Application Information MWM-J_(ii)WiringElectrical Connections• Wiring regulations on wire diameters differ from country to country. Please refer
16MWM-J_(ii) Application InformationPiping Works• Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nu
17Application Information MWM-J_(ii)Vacuuming and ChargingThe pre-charged outdoor unit does not need any vacuuming or charging. However once it is c
MWM-J_(ii) Table of ContentsTable of ContentsNomenclature...
18MWM-J_(ii) Application InformationDiagram shows typical charging method:(Mclecular-Sieve Type)Note : R22 - Nil R410A - NilCaution• For R410A, avo
19Application Information MWM-J_(ii)Special Precautions When Dealing With Refrigerant R410A Unit(1) What is new refrigerant R410A? R410A is a new H
20MWM-J_(ii) Application Information(d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure t
21Sound Data MWM-J_(ii)Sound DataSound Pressure Level ModelSpeed 1/1 Octave Sound Pressure Level (dB, ref 20μPa)Overall (dBA)Noise Criteria(RPM) 125
22MWM-J_(ii) Sound Data0102030405060125 250 500 1000 2000 4000 8000Octave-band frequency (Hz)Sound pressure level (dB,ref20μPa)High FanNC-30NC-35NC-4
23Sound Data MWM-J_(ii)0102030405060125 250 500 1000 2000 4000 8000Octave-band frequency (Hz)Sound pressure level (dB, ref20μPa)High FanMedium FanLo
24MWM-J_(ii) Sound Data0102030405060125 250 500 1000 2000 4000 8000High FanMedium FanLow FanNC-20NC-30NC-45NC-40NC-25NC-35S.Low FanOctave-band freque
25Engineering & Physical Data MWM-J_(ii)1) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).2) ALL
26MWM-J_(ii) Engineering & Physical DataEngineering Data - R410A MODELM5WM25JM5WM20JM5WM15JM5WM10JM5LC25CJM5LC20CJM5LC15CM5LC10CBtu/h 00502009710
27Performance Data MWM-J_(ii)Performance DataCalculation StepsInterpolation method can be used to get the total capacity, TC and sensible capacity,
Nomenclature MWM-J_(ii)1 M 5 WM 20 J R – A C L A B Brand M: McQuay Refrigerant “ ”: R22 4: R407C 5: R410A Product Type WM: Wall M
28MWM-J_(ii) Performance Data(b) Indoor Condition: 25°C DB, 16°C WBOutdoor Condition: 40°C DBIndoor DB˚C Indoor WB˚COutdoor DB, ˚C40TC (kW) SHC (kW)
29Performance Data MWM-J_(ii)* Repeat process (a) and (b) in 1st step for the condition below:(c) Indoor Condition: 25°C DB, 19°C WB Outdoor Con
30MWM-J_(ii) Performance Data(b) Indoor Condition: 25°C DB, 17°C WBOutdoor Condition: 40°C DBIndoor DB˚C Indoor WB˚COutdoor DB, ˚C40TC (kW) SHC (kW)
31Performance Data MWM-J_(ii)Cooling Only (R22)Model: MWM09J - MLC09CCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC
32MWM-J_(ii) Performance DataModel: MWM15J - MLC15CCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SHC PI TC SHC PI TC
33Performance Data
Performance Data MWM-J_(ii)
35Performance Data MWM-J_(ii)Heat Pump (R22)Model: MWM09JR - MLC09CRCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC S
Performance Data MWM-J_(ii)
37Performance Data MWM-J_(ii)Model: MWM15JR - MLC15CRCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SHC PI TC SHC PI
2MWM-J_(ii) Product Line-UpIndoor UnitM5WM-JM5WMNomenclatureClassifi cationPCBHandsetAir Purifi cationGrilleMarkingOthersLGSNG17Saranet FilterBio Filte
Performance Data MWM-J_(ii)
39Performance Data MWM-J_(ii)Model: MWM20JR - MLC20CRCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SHC PI TC SHC PI
Performance Data AWM-J_(ii)
Performance Data MWM-J_(ii)
Performance Data MWM-J_(ii)
43Performance Data MWM-J_(ii)Cooling Only (R410A)Model: M5WM10J - M5LC10CJCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46
44MWM-J_(ii) Performance DataModel: M5WM15J - M5LC15CJCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SHC PI TC SHC PI
45Performance Data MWM-J_(ii)Model: M5WM20J - M5LC20CJCooling Mode42416°C19°C22°C47816°C19°C22°C53616°C19°C22°C57016°C19°C22°CRemark:AFR: Air flow r
46MWM-J_(ii) Performance DataModel: M5WM25J - M5LC25CJCooling ModeRemark:AFR:EWB: Entering Wet Bulb Temp. (°C)EDB: Entering Dry Bulb Temp. (°C)TC: To
47Performance Data MWM-J_(ii)Heat Pump (R410A)Model: M5WM10JR - M5LC10CRJCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°
3Product Line-Up MWM-J_(ii)Outdoor UnitMLCMLC NomenclatureClassifi cationPCBRefrigerantControlFINSafety DevicesCompressorMarkingOthersCap TubeEXVGold
48MWM-J_(ii) Performance DataModel: M5WM10JR - M5LC10CRJHeating ModeID DB°COutdoor WB°C-9 -6 -5 6 12 15 18TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
49Performance Data MWM-J_(ii)Model: M5WM15JR - M5LC15CRJCooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SHC PI TC SHC
50MWM-J_(ii) Performance DataModel: M5WM15JR - M5LC15CRJHeating ModeID DB°COutdoor WB°C-9 -6 -5 6 12 15 18TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
51Performance Data MWM-J_(ii)Model: M5WM20J - M5LC20CJCooling ModeRemark:AFR: EWB: Entering Wet Bulb Temp. (°C)EDB: Entering Dry Bulb Temp. (°C)TC:
52MWM-J_(ii) Performance DataModel: M5WM20JR - M5LC20CRJHeating ModeID DB°COutdoor WB°C-9 -6 -5 6 12 15 18Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW
53Performance Data MWM-J_(ii)Model: M5WM25J - M5LC25CJCooling ModeRemark:AFR: EWB: Entering Wet Bulb Temp. (°C)EDB: Entering Dry Bulb Temp. (°C)TC:
54MWM-J_(ii) Performance DataModel: M5WM25JR - M5LC25CRJHeating ModeID DB°COutdoor WB°C-9 -6 -5 6 12 15 18Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW
55Outline & Dimension MWM-J_(ii)Outline & DimensionIndoor UnitModel: MWM09/15J/JR, M5WM10/15J/JR80020628850123456789 Note: Dimension in mmOu
56MWM-J_(ii) Outline & DimensionIndoor UnitModel: M(5)WM20/25J/JRNote: Dimension in mmOutdoor UnitModel: M(5)LC20/25CJ/CRJNote : Dimension in mmF
57Wiring Diagram MWM-J_(ii)Wiring DiagramCooling OnlyIndoor Unit Outdoor UnitModel: MWM09/15J Model: MLC09/15CJ M5WM10/15J M5LC10/15CJ70034 1019
4MWM-J_(ii) Product Line-UpIndoor UnitM5WMM5WMNomenclatureClassifi cationPCB HandsetAir Purifi cationGrilleMarkingOthersLGSN GS01 Saranet FilterBio Fil
58MWM-J_(ii) Wiring DiagramCooling OnlyIndoor Unit Outdoor UnitModel: MWM20/25J Model: MLC20/25C70034 108883
59Wiring Diagram MWM-J_(ii)70034 101944Heat PumpIndoor Unit Outdoor UnitModel: MWM09/15JR Model: MLC09/15CRJ M5WM10/15JR M5LC10/15CRJ
60MWM-J_(ii) Wiring Diagram70034 108882Heat PumpIndoor Unit Outdoor UnitModel: MWM20/25JR Model: MLC20/25CR
61Wiring Diagram MWM-J_(ii)70034 108883Cooling OnlyIndoor Unit Outdoor UnitModel: M5WM20/25J Model: M5LC20/25CJ
62MWM-J_(ii) Wiring Diagram70034 108882Heat PumpIndoor Unit Outdoor UnitModel: M5WM20/25JR Model: M5LC20/25CRJ
63Service & Maintenance MWM-J_(ii)Service & MaintenanceWarning• Disconnect from main supply before servicing the air conditioner.• The unit
64MWM-J_(ii) Service & MaintenancePre Start Up Maintenance(After Extended Shutdown)• Inspect thoroughly and clean indoor and outdoor units.• Cl
65Troubleshooting MWM-J_(ii)TroubleshootingIndicator LightsIR Signal ReceiverWhen an infra red remote control operating signal has been transmitted,
66MWM-J_(ii) TroubleshootingLED Indoor Lights: Normal Operation and Fault Conditions for Cooling / Heat Pump Unit1COOL/HEAT(GREEN/RED)Error CodeNorm
67Troubleshooting MWM-J_(ii)Error Code / Fault ConditionWhen a malfunction of the air conditioner unit is detected, immediately switch off the main p
5Application Information MWM-J_(ii)Application InformationOperating RangeEnsure the operating temperature is in allowable range.Cooling onlyNote :St
68MWM-J_(ii) TroubleshootingDiagnostic GuidelinesBy means of pressure readings:DataCircuitPressureProbable causeToo lowA little lowNormalA little hig
69Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeExplo
70MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeINDOO
71Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeINDOO
72MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeINDOO
73Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
74MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
75Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
76MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
77Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
6MWM-J_(ii) Application InformationRefrigerant Circuit DiagramModel: MWM09J - MLC09C M5WM10J - M5LC10CJ MWM15J - MLC15C M5WM15J - M5LC1
78MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
79Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
80MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
81Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
82MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
83Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
84MWM-J_(ii) Exploded View & Part ListNote: All exploded view and part list are subjected to change by the manufacturer without prior noticeNo De
85Exploded View & Part List MWM-J_(ii)Note: All exploded view and part list are subjected to change by the manufacturer without prior noticeOUTDO
© 2011 McQuay International www.mcquayup.com Products manufactured in an ISO certified facility. This document contains the most current product infor
7Application Information MWM-J_(ii)Model: MWM25J - MLC25CModel: MWM09JR - MLC09CR M5WM10JR - M5LC10CRJ M5WM15JR - M5LC15CRJ 70034 023154
Revision History List Manual : Wall Mounted Split System TM : MWM-J_(ii) Revision Subject Amendment on Manual’s Page No. Date 01 1. Correctio