48
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW FACIA.
MMSD2020A
2 x MCK020C
Btu/h 2 x 18000
W
2 x 5280
ONE UNIT RUNNING W
2106
TWO UNITS RUNNING W
4628
ONE UNIT RUNNING A 10.3
TWO UNITS RUNNING A 22.1
W/W 2.28
V/Ph/Hz 220 ~ 240 / 1 / 50
R22 / CAPILLARY TUBE
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
l/s / cfm
212 / 450
l/s / cfm
203 / 430
l/s / cfm 194 / 410
EXTERNAL STATIC PRESSURE (H/M/L) Pa/in.wg. N/A
dBA 47 / 46 / 44
mm/in 250 (295) / 9.8 (11.6)
mm/in 570 (640) / 22.4 (25.2)
mm/in 570 (640) / 22.4 (25.2)
mm/in 317 (127) / 12.5 (5.0)
mm/in
630 (700) / 24.8 (27.6)
mm/in
630 (700) / 24.8 (27.6)
kg/lb
23 + 2 / 51 + 4
mm/in 19.1 / ¾
l/s / cfm 1132.7 / 2400
dBA 61
mm/in 632 / 24.9
mm/in 690 / 37.8
mm/in 437 / 17.2
mm/in
824 / 32.4
mm/in
1194 / 47.0
mm/in
611 / 24.1
kg/lb 106 / 234
FLARE VALVE
LIQUID mm/in 2 X 2.4 / 2 X ¼
GAS mm/in 2 X 15.9 / 2 X ⅝
kg/lb 2 X 1.83 / 2 X 4.03
REFRIGERANT CHARGE
UNIT WEIGHT
PIPE CONNECTION
TYPE
SIZE
PACKING
DIMENSION
HEIGHT
WIDTH
DEPTH
WIDTH
DEPTH
UNIT WEIGHT
CONDENSATE DRAIN SIZE
OUTDOOR UNIT
AIR FLOW
SOUND PRESSURE LEVEL
UNIT DIMENSION
HEIGHT
PACKING
DIMENSION
HEIGHT
WIDTH
DEPTH
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
HEIGHT
WIDTH
DEPTH
REFRIGERANT TYPE / CONTROL
INDOOR UNIT
CONTROL
AIR FLOW
HIGH
MEDIUM
LOW
EER
POWER SOURCE
NOMINAL CAPACITY
NOMINAL TOTAL INPUT
POWER
NOMINAL RUNNING
CURRENT
MODEL
OUTDOOR UNIT
INDOOR UNIT
General Data - Cooling Only (R22)