Fresh Air Intake For M5CKX-C Unit
Take off the panel from the indoor unit
Remove the PE foam from the drain pan and another one on the unit.
Remove the pre-punched panel on the CKC unit with a screwdriver.
The diameter of the air intake knock out hole is 65mm.
Then, fix the fresh air kit (refer to parts list) to the hole. Finally, a flexible duct is connected to let the fresh air
moving in.
The direction of the fresh air intake is shown as fig. 2.
Sealing Material
It is possible to seal one of the four air discharge outlet (sealing two or more air discharge outlet could cause
a malfunction).
Remove the front panel and inserting the seal material into the air discharge outlet at the indoor unit to
sealthe air outlet.
The sealing material is the same length as the length air discharge outlet. If it is desired to seal the shorter
air discharge outlet, cut the sealing material to shorten it.
Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not
touch the air louver. Be sure not to push the sealing material in any farther than about 10mm.
Fig. 2