
12 OM 1191
Parameters
Parameter List
The following parameters are important on Daikin applications. A summary is shown in Table 63: Parameter Settings onpage
89. Allothershouldnotbeadjusted.ParameterdataisspecifictoMD5firmwareversion2.13.
Group 99: Start-Up Data
ThisgroupdenesspecialStart-updatarequiredto:
• Set up the drive.
• Enter motor information
NOTE: Parameters checked under the heading “S” can be
modied only when the drive is stopped.
Table 4: Group 99: Start-up Data
Code Description Range Resolution Default S
9901 LANGUAGE 0…16 1
0
(ENGLISH)
Selects the display language.
0 = ENGLISH 1 = ENGLISH (AM) 2 = DEUTSCH 3 = ITALIANO 4 = ESPAÑOL 5 = PORTUGUES
6 = NEDERLANDS 7 = FRANCAIS 8 = DANSK 9 = SUOMI 10 = SVENSKA 11 = RUSSKI
12 = POLSKI 13 = TÜRKCE 14 = CZECH 15 = MAGYAR 16 = RESERVED
9902 APPLIC MACRO -3…15, 31 1
1(HVAC
DEFAULT)
Selects an application macro. Application macros automatically edit parameters to congure the MD5 for a particular application. See Application macros for
application macro descriptions.
1= HVAC DEFAULT 2= SUPPLY FAN 3= RETURN FAN 4= COOLING TOWER FAN 5= CONDENSER
6= BOOSTER PUMP 7= PUMP ALTERNATION 8= INTERNAL TIMER 9= INTERNAL TIMER WITH CONSTANT SPEEDS
10= FLOATING POINT 11= DUAL SETPOINT PID 12= DUAL SETPOINT PID WITH CONSTANT SPEEDS
13= E-BYPASS 14= HAND CONTROL 15= E-CLIPSE
31 = LOAD FD SET - FrontDrop parameter values as dened by the FlashDrop le. Parameter view is selected by parameter 1611 PARAMETER VIEW.
• FlashDrop is an optional device for fast copying of parameters to unpowered drives. FlashDrop allows easy customization of the parameter list, e.g.
selected parameters can be hidden. For more information, see MFDT-01 FlashDrop User’s Manual [3AFE68591074 (English)].
-1 = USER S1 SAVE, -3 = USER S2 SAVE - With these it is possible to save two different user parameter sets into the drive permanent memory for later use.
Each set contains parameter settings, including Group 99: START-UP DATA, and the results of the motor identication run.
0 = USER S1 LOAD, -2 = USER S2 LOAD - With these the user parameter sets can be taken back in use.
9905 MOTOR NOM VOLT
115…345 V
(200 V, US)
230…690 V
(400 V, US)
288…862 V
(600 V, US)
1 V
1 V
1 V
230 V (US)
460 V (US)
575 V (US)
Denes the nominal motor voltage.
• Must equal the value on the motor rating plate.
• The MD5 cannot supply the motor with a voltage greater than the input power (mains) voltage.
9906 MOTOR NOM CURR
0.15 · I2
n
…
1.5 · I2
n
0.1 A 1.0 · I2
n
Denes the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: 0.15…1.5 · I2
n
(where I2
n
is drive current).
9907 MOTOR NOM FREQ
10.0…500.0
Hz
0.1 Hz
60.0 Hz
(US)
Denes the nominal motor frequency.
• Range: 10…500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the MOTOR NOM VOLT.
• Field weakening point = Nom Freq · Supply Volt / Mot Nom Volt
9908 MOTOR NOM SPEED
50…30000
rpm
1 rpm
Size
dependent
Denes the nominal motor speed.
• Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER
0.15…
1.5 · P
n
0.1 hp 1.0 · P
n
Denes the nominal motor power.
• Must equal the value on the motor rating plate.
Parameters
Comentários a estes Manuais