McQuay Service Guide Book
36
6.4 Multi Split Conversion
Cooling Only Model (L2.0 / L208A)
The cooling only model WM-G, CK-A/B/C/E, CE-E, CC-C which are using L2 control board can be
switched to multi split units without any modification needed.
Heatpump Model (L2.0)
WM-GR
The Multi Split mode can be selected at the slide switch on the On/Off Switch Board; Preset at OFF.
The outdoor coil sensor has to be removed from the PCB as the reading is taken from the outdoor
PCB directly.
Heatpump Models (L208A)
CK-AR/BR/CR/ER, CE-ER, CC-CR (L208A)
The multisplit can be selected by using shunt jumper and short jumper header MODEL_KP between
pin 1 & 2 as the picture shown below. The outdoor coil sensor has to be removed from the PCB as the
reading is taken from the outdoor PCB directly.